VAT

Schneider LC1D Coil Codes Explained

Schneider LC1D Coil Codes Explained – B7, BD, F7, P7, U7, V7 & N7

Choosing the correct Schneider LC1D contactor coil voltage is essential when ordering or replacing a TeSys Deca contactor.

Two LC1D contactors can have the same current rating and look almost identical but have completely different control coil voltages.

For example:

LC1D18B7 = 18A contactor with a 24V AC coil

LC1D18BD = 18A contactor with a 24V DC coil

The small difference between B7 and BD is therefore extremely important.

This guide explains the most common Schneider LC1D coil codes and how to identify the correct contactor.

Schneider LC1D Coil Code Table

Schneider Coil Code Coil Voltage Supply Type
B7 24V AC 50/60Hz
BD 24V DC
E7 48V AC 50/60Hz
ED 48V DC
F7 110V AC 50/60Hz
FD 110V DC
M7 220V AC 50/60Hz
P7 230V AC 50/60Hz
U7 240V AC 50/60Hz
Q7 380V AC 50/60Hz
V7 400V AC 50/60Hz
N7 415V AC 50/60Hz
R7 440V AC 50/60Hz

These are some of the most commonly encountered coil codes. Other Schneider coil voltages and electronic wide-range coils are also available depending on the specific TeSys Deca contactor.

What Does the Coil Code Mean?

Schneider adds the coil-voltage code to the end of the base contactor part number.

For example:

LC1D18B7

can be broken down as:

  • LC1D – Schneider TeSys Deca contactor

  • 18 – 18A contactor rating

  • B7 – 24V AC 50/60Hz coil

Similarly:

LC1D25F7

means:

  • LC1D contactor

  • 25A rating

  • 110V AC 50/60Hz coil

And:

LC1D32P7

means:

  • LC1D contactor

  • 32A rating

  • 230V AC 50/60Hz coil

B7 vs BD – What's the Difference?

This is one of the most important Schneider LC1D distinctions.

B7

B7 = 24V AC 50/60Hz

Example:

LC1D18B7

This is an LC1D18 contactor with a 24V AC control coil.

BD

BD = 24V DC

Example:

LC1D18BD

This is an LC1D18 contactor with a 24V DC control coil.

Although the two part numbers look very similar, the coil supply is completely different.

A B7 contactor should not be ordered as a replacement for a BD contactor simply because both say 24V.

Always establish whether the control circuit is AC or DC.

What Does F7 Mean on a Schneider Contactor?

F7 = 110V AC 50/60Hz.

For example:

LC1D25F7

is a Schneider LC1D25 contactor fitted with a 110V AC coil.

110V AC control circuits are commonly found in industrial machinery and control panels.

What Does P7 Mean?

P7 = 230V AC 50/60Hz.

For example:

LC1D32P7

is an LC1D32 contactor with a 230V AC coil.

This is one of the common coil voltages used in UK and European control systems.

What Does U7 Mean?

U7 = 240V AC 50/60Hz.

Schneider distinguishes this from P7, although 230V and 240V systems exist within the same harmonised European voltage environment.

When replacing an existing contactor, the safest approach is to match the complete existing part number wherever possible.

What Does V7 Mean?

V7 = 400V AC 50/60Hz.

For example:

LC1D18V7

is an 18A LC1D contactor fitted with a 400V AC coil.

This should not be confused with the main motor voltage.

The V7 suffix specifically identifies the control coil voltage.

What Does N7 Mean?

N7 = 415V AC 50/60Hz.

An example would be:

LC1D25N7

which is an LC1D25 contactor with a 415V AC coil.

415V coil contactors are still commonly encountered in UK industrial installations.

Is the Coil Voltage the Same as the Motor Voltage?

Not necessarily.

This is one of the most common mistakes when selecting a contactor.

A motor may operate from a 400V three-phase supply, while the contactor coil may operate from:

  • 24V AC

  • 24V DC

  • 110V AC

  • 230V AC

  • 240V AC

  • 400V AC

  • 415V AC

The motor supply and control circuit therefore need to be checked separately.

For example, a 400V three-phase motor controlled by a 24V AC control transformer might use an:

LC1D18B7

not an LC1D18V7.

How Do I Find the Coil Voltage on an Existing LC1D Contactor?

The easiest method is to locate the complete Schneider part number on the existing contactor.

Look for a reference such as:

LC1D09B7
LC1D12BD
LC1D18F7
LC1D25P7
LC1D32U7

The final characters identify the coil version.

If the full part number cannot be read, check any separate voltage marking on the coil or side label.

If you are still unsure, send Western Automation a clear photograph showing:

  • Front of the contactor

  • Side label

  • Existing part number

  • Coil terminals or coil marking

and we can help identify the correct replacement.

Common LC1D Part Number Examples

LC1D09B7

LC1D09 – 9A contactor
B7 – 24V AC coil

LC1D12BD

LC1D12 – 12A contactor
BD – 24V DC coil

LC1D18F7

LC1D18 – 18A contactor
F7 – 110V AC coil

LC1D25P7

LC1D25 – 25A contactor
P7 – 230V AC coil

LC1D32U7

LC1D32 – 32A contactor
U7 – 240V AC coil

LC1D38N7

LC1D38 – 38A contactor
N7 – 415V AC coil

The same principle applies across many Schneider TeSys Deca contactors.

What Does the Number 7 Mean?

For conventional Schneider AC coil codes, the final 7 normally indicates a coil designed for 50/60Hz operation.

Examples include:

  • B7 – 24V AC 50/60Hz

  • F7 – 110V AC 50/60Hz

  • P7 – 230V AC 50/60Hz

  • U7 – 240V AC 50/60Hz

  • V7 – 400V AC 50/60Hz

  • N7 – 415V AC 50/60Hz

Older or less common Schneider contactors may also be encountered with suffixes ending in 5 or 6, relating to different frequency specifications.

For a replacement, matching the complete part number remains the safest approach.

What Does D Mean on the End of a Schneider Coil Code?

On many conventional Schneider coil references, D indicates a DC coil.

Examples include:

  • BD = 24V DC

  • ED = 48V DC

  • FD = 110V DC

  • MD = 220V DC

This makes the distinction between B7 and BD particularly important.

What Are Schneider Electronic Coil Codes?

Some newer Schneider TeSys contactors use electronic wide-range coils rather than one fixed coil voltage.

Examples used across applicable TeSys Deca contactors include:

Electronic Coil Code Typical Control Range
BNE 24–60V AC/DC
EHE 48–130V AC/DC
KUE 100–250V AC/DC

These wide-range coils can simplify stockholding because one contactor can cover several traditional control voltages.

Always check that the electronic coil option is available for the specific LC1D contactor frame being selected.

Can I Replace B7 With BD?

No, not simply because both are rated at 24V.

B7 is 24V AC.

BD is 24V DC.

The control supply type must match the contactor coil.

Using the wrong coil specification can result in the contactor failing to operate correctly or potentially being damaged.

Can I Replace P7 With U7?

P7 and U7 are different nominal coil codes:

P7 = 230V AC

U7 = 240V AC

Do not automatically substitute one for the other without checking Schneider's specification and the actual control supply.

When replacing an existing unit, matching the existing suffix is normally preferable.

Can I Replace V7 With N7?

V7 and N7 refer to different nominal voltage codes:

V7 = 400V AC

N7 = 415V AC

Schneider notes that equipment rated around European harmonised supply voltages may cover wider operating ranges, but replacement selection should still be based on the exact contactor specification and control voltage.

If the original contactor is N7, use the corresponding N7 replacement unless Schneider documentation confirms otherwise.

Why Does Coil Voltage Matter?

The contactor coil creates the magnetic field that pulls the contactor closed.

If the applied control voltage is wrong, the contactor may:

  • Fail to pull in

  • Chatter

  • Drop out

  • Run unusually hot

  • Fail prematurely

  • Damage the coil

For this reason, coil voltage is just as important as choosing the correct contactor current rating.

Need Help Identifying a Schneider LC1D?

Western Automation supplies an extensive range of Schneider TeSys Deca LC1D contactors in common current ratings and coil voltages.

If you are replacing an existing contactor, send us:

  • The full Schneider part number

  • A photograph of the existing contactor

  • Motor kW

  • Motor full-load current

  • Control voltage

  • Whether the control supply is AC or DC

We can help identify the correct LC1D contactor, coil voltage, overload relay and compatible accessories.

For help selecting the correct contactor size, see our Schneider LC1D Contactor Selection Guide – Which LC1D do I need?

Schneider LRD Overload Selection Guide – Which LRD Fits My LC1D Contactor?

Oct 02 2026 | Guides and How-to